SY6 - Thermal-Protectors with insulation cap
Thermik ® 3D Product-Viewer
Just click on the picture to rotate the product atomaticly or use the arrow buttons. To display more information just hover the "Hot-Spots".
Further information for this
product for download
Data sheet (PDF)
Product pictures (JPG/ZIP)
3D Data (STEP-Format)
Contactor SY6 - request at
Thermik without obligation...
Technical details of SY6:
Every important detail at a glance!
Automatic resetting, for star point connection to protect a three phase motor
Contact type: normally closed
Nominal switching temperature (NST) in steps of 5 °C:
70 °C - 180 °C
Standard tolerance: ± 5K
Reset temperature range below NST (UL / CSA):
depends on NST
Operating voltage … AC / DC - available,
values on inquiry: up to 480 V ~Rated voltage UAC: 3 x 440 V / 50/60 Hz
Rated current AC cos φ = 1.0 (ohmic load) / switching cycles:
2.5 A / 10,000
6.3 A / 3,000*Rated current AC cos φ = 0.6 acc. to IEC 60730-2-9 / switching cycles:
1.6 A / 10,000
Contact bounce time: < 1 ms
Contact resistance (acc. to MIL-Std. R 5757): < 50 mΩ
Impregnation resistance with- or without resin
(acc. to requirements)*: suitableVibration proof at 10 … 60 Hz: 100 m/s²
Pressure stability of housing *: 600 N
High voltage insulation (not C - versions): 2 kV
Suitable for protection class I or II: suitable
Standard wiring connection: lead wire 0.5 mm² / AWG 20
Diameter: 9.8 mm
Heigth: 7,6 mm
Length of insulation cap: 17.0 mm
Approvals available (according to design): UL; CSA